HVACCalc.

AC tonnage calculator

The nominal size of central air conditioner a house needs, in tons and BTU per hour, from its floor area and climate zone — plus the exact calculated load so you can see how much the rounding to a half-ton step is costing you.

The result below is the worked example already filled in. Change a field and press the button to see your own numbers; the result updates in place.

Your answer

4 tons air conditioner

44,000 BTU/h calculated load · 3.7 tons exact · 1,600 CFM of airflow

Cooling load 44,000 BTU/h 2,000 sq ft in zone 2 — hot
Load in tons 3.7 tons One ton of cooling is 12,000 BTU/h — a unit definition, not a weight
Nominal size to buy 4 tons (48,000 BTU/h) Rounded up to the next half ton
Airflow 1,600 CFM 400 CFM per ton; below 350 CFM/ton the coil can ice and the charge cannot be set
Duct trunk, round metal 18 in At 0.1 in. w.c. per 100 ft — check with the duct calculator
Floor area per ton 500 sq ft A useful sanity check: most U.S. homes land between 400 and 700 sq ft per ton
  • Zone 2 — hot uses 22 BTU per sq ft as the starting point, adjusted for 8 ft ceilings and average insulation.
  • The nominal size is the smallest standard size that still covers the calculated load. Never round down to save money on equipment.

Before you buy

  • A tonnage chart cannot see your house. Two 2,000 sq ft houses in the same zip code can differ by a ton because of attic insulation, window area and duct location.
  • Do not accept "we always put a 4-ton in a house this size" as the sizing method. Ask for the Manual J room-by-room report; it is normal to receive it.
  • A 5-ton unit is the largest common residential size. If the load calls for more, the answer is usually envelope work or two systems, not a bigger single unit.

Sizes either side

  • 3.5 ton — smaller — only if the load is genuinely lower than this estimate
  • 4.5 ton — larger — gives headroom but costs more to run and dehumidifies worse

What “tonnage” means

A ton of cooling is 12,000 BTU per hour. The word comes from the ice that early refrigeration replaced: a ton of ice absorbed 12,000 BTU/h as it melted. Nothing about a modern condensing unit weighs a ton, and the tonnage is not a measure of how much refrigerant or metal it contains. It is simply a shorthand for capacity, and the equipment catalogue is built in half-ton steps between 1.5 and 5 tons.

That shorthand hides a range. A “3-ton” unit delivers 36,000 BTU/h at AHRI rated conditions, which are 95°F outdoor air and 80°F dry-bulb / 67°F wet-bulb indoor air. On a 105°F afternoon in Arizona it delivers less. In a humid climate, part of the capacity goes to water rather than temperature. This calculator works in nominal tons because that is what you can buy, and shows the exact load because that is what the house actually needs.

How the tonnage is calculated here

The cooling load is built from the same model as the BTU calculator: floor area × climate-zone BTU per square foot × ceiling factor × insulation factor, with no adjustment for people, kitchen or windows because a whole-house sizing decision should not hinge on a family’s dinner. The load in BTU/h is divided by 12,000 to get exact tons, and then rounded up to the next half ton.

Rounding up is deliberate. Rounding down produces a unit that runs continuously on the design day and never quite reaches the thermostat setting, which is worse for comfort and for the compressor than half a ton of headroom. The result table also shows the floor area per ton, which is the sanity check most contractors carry in their heads: between roughly 400 and 700 sq ft per ton for a U.S. house.

Why square footage alone is not a sizing method

Two houses of the same size on the same street can need different tonnage. The variables that move a load are the ones a floor plan cannot show: attic insulation depth, window area and orientation, whether the ducts run through a 140°F attic, how much air leaks through the top plate, the colour and pitch of the roof, and whether the house sits in shade for half the afternoon. A west-facing wall of single glazing can add close to a ton on its own.

Manual J, the ACCA standard, turns those variables into a room-by-room load. It is required by national building codes and by most states and municipalities for new construction and equipment replacement, and a contractor who cannot produce one is either using a shortcut or using software they do not want to explain. The output is a page per room with sensible and latent loads, and it is normal to ask for a copy.

This calculator is a screening tool, not a substitute. Its job is to tell you whether a quote is in the right range before you spend an evening getting three of them.

What oversizing actually does

The instinct is that a bigger unit is safer: it will cope with the hottest day and cool the house faster. In practice an oversized air conditioner reaches the thermostat setpoint quickly, shuts off, and leaves the indoor humidity high because the coil did not run long enough to drain water. The house feels cold and clammy at the same time. Then it short-cycles: repeated starts wear the compressor and contactor, waste energy on each start, and make the temperature swing.

ENERGY STAR makes the same point on its room air conditioner page, and it applies to central systems too. A right-sized variable-speed or two-stage unit runs longer at lower capacity, which is quieter, dehumidifies better and holds a steadier temperature. When the calculated load falls between two sizes, the smaller unit with a variable-speed compressor is often the better buy.

Airflow, ducts and the number nobody quotes

A 3-ton system needs about 1,200 CFM of air. That airflow is set by the blower and limited by the ductwork: a system with undersized ducts delivers maybe 900 CFM, and the coil then runs cold, the capacity drops and the evaporator can ice. The DOE Building America programme puts the practical limit at 0.4 to 0.5 in. w.c. of total external static pressure, which includes the filter, the coil, the supply trunk and the return.

This is why replacing a unit without touching the ducts often disappoints. If the new condenser is the same size as the old one, the ducts are probably the same too, and the same restriction remains. Ask for the static pressure measurement after installation; a good installer takes it.

When the answer is not a new air conditioner

If the load comes out above 5 tons, the usual answer is not a bigger single unit. Residential equipment stops there for good reasons: the line set, the electrical circuit and the duct size all become impractical. The options are two systems (one per floor), a zoned system with a single variable-speed outdoor unit, or envelope work that removes the load in the first place. Attic insulation to the DOE target and air sealing are usually cheaper per ton than equipment.

If the load is small, below 1.5 tons, a ducted central system may be the wrong shape entirely. A ductless mini-split or a window unit can cover one or two rooms without the duct losses.

Frequently asked

What size AC do I need for a 2,000 sq ft house?

In zone 2 (hot) this model gives about 44,000 BTU/h, which rounds to a 4-ton unit. In zone 4 the same house lands near 36,000 BTU/h and a 3-ton unit, and in zone 6 near 30,000 BTU/h and a 2.5-ton unit. A Manual J can move any of those by half a ton.

Is 1 ton enough for 600 square feet?

At 400 to 500 sq ft per ton, 600 sq ft is 1.2 to 1.5 tons. In a hot climate it is 1.5 tons; in a cool climate with good insulation it can be 1 ton. The calculator shows the number rather than the ratio.

Why do contractors quote whole and half tons?

Residential equipment is manufactured in half-ton steps from 1.5 to 5 tons: 18,000, 24,000, 30,000, 36,000, 42,000, 48,000 and 60,000 BTU/h. You cannot buy a 3.2-ton condenser, so the calculated load is rounded up to the next available size.

Does a bigger AC cool faster?

It cools the air faster and the house worse. An oversized unit reaches the thermostat before it has run long enough to condense moisture, so the room feels cold and damp and the compressor short-cycles. Longer run times at lower capacity are what good systems do.

How many CFM does a 3-ton system need?

About 1,200 CFM at 400 CFM per ton. Below roughly 350 CFM per ton the coil runs too cold, can ice, and the refrigerant charge cannot be verified properly. Above 450 CFM per ton the coil removes less humidity.

Can I replace a 3-ton unit with a 2.5-ton unit?

Often yes, if a Manual J shows the old unit was oversized. The ductwork, line set and electrical may also need changes. Never downsize on a guess: a unit that is too small for the design day runs continuously and never reaches the setpoint.

Where these numbers come from

Numbers that come from our own arithmetic rather than a published table are marked house rule on the method page. No price appears anywhere on this site: no supplier publishes a national one, and an invented number would be worse than no number.