Mini-split size calculator
Room-by-room BTU, the head size for each zone, and the outdoor unit that can run them all — with the connection ratio that manufacturers actually limit you by.
The result below is the worked example already filled in. Change a field and press the button to see your own numbers; the result updates in place.
Your answer
24,000 BTU/h outdoor unit
3 × 9,000 BTU/h heads · 113% connection ratio · 27,000 BTU/h connected
| Load per room | 7,000 BTU/h | 350 sq ft × 20 BTU/sq ft, adjusted |
| Head size per room | 9,000 BTU/h | Nearest standard head at or above the room load |
| Total connected capacity | 27,000 BTU/h | 3 heads × 9,000 BTU/h |
| Outdoor unit | 24,000 BTU/h (2 tons) | Sized at 85% diversity, then checked against the 130% limit |
| Connection ratio | 113% | Connected indoor capacity ÷ outdoor capacity |
| Rooms per ton | 1.5 | A rough check; room layout matters more than this number |
- Zone 3 — warm at 20 BTU per sq ft, with a 1.00 ceiling factor and 1.00 insulation factor.
- The 85% diversity factor assumes the bedrooms and the living room are not all at full load at the same moment. It is a house rule; the manufacturer connection chart overrides it.
Before you buy
- Multi-zone outdoor units are deliberately smaller than the sum of the indoor heads, because not every room calls for full cooling at once. A 100% to 130% connection ratio is normal.
- Line length and height matter: long refrigerant runs lose capacity. Keep runs inside the manufacturer chart and add charge per the installation manual.
- One oversized head in a small bedroom will short-cycle and leave the room humid. When in doubt between two head sizes, take the smaller one.
Zoning is the point of a mini-split
A ducted system makes one temperature for the whole house and then argues with the rooms that disagree. A ductless mini-split puts an indoor head in each space, each with its own thermostat, and an outdoor unit that can run several heads at once. That is why the sizing question is not “what size for the house” but “what size for each room, and what outdoor unit can serve them together”.
The calculator takes an average room size for simplicity. In a real design each room gets its own load, and a west bedroom with a glass wall may need a 12,000 BTU/h head while an identical bedroom on the north side needs 9,000. Use the number here to get the shape of the system, then refine room by room.
Head sizes and why they are coarse
Ductless heads come in standard capacities: 9,000, 12,000, 15,000, 18,000, 24,000, 30,000 and 36,000 BTU/h. A 7,000 BTU/h room gets a 9,000 BTU/h head because there is nothing smaller in most lines. That half-ton of headroom is usually fine in a living room and less fine in a small bedroom, where an oversized head reaches the setpoint in a few minutes, shuts off, and never dries the air.
The practical rule is to choose the smallest head that covers the load, and to prefer a variable-speed model with a wide turndown range over a single-speed one. A head that can throttle to 20% of capacity behaves like a much smaller unit for most of the year.
Connection ratio and diversity
A multi-zone outdoor unit is deliberately smaller than the sum of its indoor heads. If four heads add up to 48,000 BTU/h, the outdoor unit might be 36,000 BTU/h, on the assumption that the bedrooms and the living room are not all at full load at 4 p.m. The manufacturer publishes the allowed range, commonly 100% to 130% of the outdoor capacity.
This calculator uses an 85% diversity factor to pick a starting outdoor size, then raises it if the connection ratio would exceed 130%. Both numbers are house rules around the manufacturer chart, which always wins. If you are choosing equipment, take the head list and the ratio to a dealer and ask them to check it against the model’s connection table.
| Connection ratio | What it means |
|---|---|
| Below 100% | Outdoor unit is larger than the heads; capable but paying for capacity you cannot use |
| 100% – 130% | Typical design range; all zones can run, though not always at full capacity together |
| Above 130% | Outside most manufacturer charts; some zones will be starved when others call |
What a mini-split does not solve
A ductless head heats and cools the room it is in. It does not fix a cold bathroom at the end of a corridor, and it does not ventilate: a mini-split recirculates indoor air and has no fresh-air intake. If the house needs fresh air, that is a separate ventilation decision, not a bigger head.
It also does not distribute air around corners. Manufacturers publish a throw distance, and furniture, curtains and half-walls defeat it. A head mounted above a wardrobe blows into the wardrobe. Plan the furniture before the electrician arrives.
Installation details that change performance
Refrigerant line length and height difference cost capacity. Every manufacturer sets a maximum run and a maximum elevation change, and additional refrigerant charge is required beyond a stated length. A long run to a detached garage may be outside the chart even though the head is the right size.
Condensate has to go somewhere. Indoor heads produce water in cooling mode, and a gravity drain is preferable to a pump. A pump that fails stains a ceiling. Outdoor units need clearance for airflow, a stand above snow level, and a location away from bedrooms and roof drip lines. In cold climates, defrost water must be able to drain away rather than freeze under the unit.
Single-zone versus multi-zone
A single-zone system is one head and one outdoor unit. It is the most efficient configuration per dollar and the right answer for a garage conversion, an addition or one problem room. A multi-zone system costs more, has more joints and more to go wrong, but replaces a whole-house system in a house without ducts.
For a whole house, compare three options: a multi-zone ductless system, a ducted heat pump if ducts exist and are in good condition, and a hybrid where a ducted system handles the main floor and one head serves an addition. The heat pump calculator covers the ducted case.
What this calculator cannot tell you
It assumes every room is the same size and has the same exposure, which is never true. It does not model line length, defrost, altitude, ceiling height variation or the manufacturer’s connection chart. It also does not know whether the electrical panel has capacity for another outdoor unit, or whether the wall you want to use is load bearing. Treat the output as a shopping list to discuss, not an order.
Frequently asked
What size mini-split for a 350 sq ft room?
In zone 3 with average insulation this model gives about 7,000 BTU/h, so a 9,000 BTU/h head. A sunny room with large windows can justify 12,000; a shaded, well-insulated bedroom may be comfortable on 9,000 even at 400 sq ft.
How many rooms can one outdoor unit run?
Most residential multi-zone units accept two to five indoor heads, and some accept eight. The limit is the manufacturer’s connection chart, not a rule of thumb: each model lists the maximum number of heads, the maximum connected capacity and the minimum load per zone.
What is a connection ratio?
The total capacity of the indoor heads divided by the outdoor unit’s capacity. Multi-zone systems are usually designed between 100% and 130%, because not every room calls for full output at once. Above the manufacturer’s maximum, the system cannot deliver rated capacity to all zones.
Is one big head cheaper than several small ones?
Usually, but it conditions one space. A single head in a hallway cannot push conditioned air into closed bedrooms, and a head that is too large for a small room short-cycles and leaves it humid. Zoning is the reason to buy a multi-split in the first place.
Do mini-splits work in cold climates?
Cold-climate ductless units are rated to run at 5°F and below, and ENERGY STAR’s Cold Climate criteria require at least 70% of 47°F capacity at 5°F. In a cold climate, check the low-temperature capacity table and plan a backup heat source for the coldest nights.
Where should the indoor head go?
High on a wall, with a clear path across the room, not blowing directly at a bed or sofa, and not above a heat source. Keep it away from corners that trap air and from doorways where it short-circuits. The outdoor unit needs clearance, drainage and a stand above snow.
Where these numbers come from
- Heat Pump Systems — U.S. Department of Energy, Energy Saver, read Nov 20, 2026
- Air-Source Heat Pumps — key product criteria — U.S. EPA ENERGY STAR, read Nov 20, 2026
- ACCA Technical Manuals — Manual J, S, D and H — Air Conditioning Contractors of America (ACCA), read Nov 20, 2026
Numbers that come from our own arithmetic rather than a published table are marked house rule on the method page. No price appears anywhere on this site: no supplier publishes a national one, and an invented number would be worse than no number.
Next: ducted heat pump sizing · BTU calculator · AC tonnage · BTU per square foot