HVACCalc.

Method and sources

Every calculator on this site shows its formula, and every published number has a source with a URL and the date it was read. This page is the complete list, including the numbers that are ours rather than anyone else’s.

The one thing to understand first

These are screening tools. They answer “is this quote in the right range?” and “which size should I be asking about?”. They do not answer “what is the load on this house?”. That question needs Manual J, the ANSI-approved residential load calculation published by ACCA, and a contractor who will show you the room-by-room report. ACCA states that a proper load calculation is required by national building codes and by most states and municipalities, which is why asking for one is a normal request rather than an insult.

Every calculator page carries a “what this calculator cannot tell you” section for the same reason. A number without its limits is worse than no number, because it invites a purchase.

Cooling load

cooling BTU/h = area × zone cooling factor × (ceiling ÷ 8) × insulation factor × window factor
+ 600 × (people − 2, never below zero) + 4,000 if there is a kitchen

The 600 BTU/h per person and the 4,000 BTU/h kitchen adder are ENERGY STAR’s published room air conditioner adjustments. The ceiling multiplier is our arithmetic on ENERGY STAR’s note that the chart assumes an 8 ft ceiling. The insulation factors (0.85 good, 1.00 average, 1.15 poor) and window factors (0.95, 1.00, 1.08) are house rules: reasonable ranges, not published coefficients.

ZoneCooling BTU/sq ftHeating BTU/sq ftWinter design temp
1 — Miami FL, Honolulu HI, San Juan PR241040°F
2 — Orlando FL, Houston TX, Phoenix AZ221530°F
3 — Atlanta GA, Dallas TX, Los Angeles CA202025°F
4 — Philadelphia PA, Nashville TN, St. Louis MO182515°F
5 — Boston MA, Chicago IL, Denver CO16305°F
6 — Minneapolis MN, Milwaukee WI, Burlington VT1535-5°F
7 — Fargo ND, Duluth MN, Caribou ME1440-15°F
8 — Fairbanks AK, Utqiaġvik AK1345-25°F

The zone factors are the biggest house rule on the site. They are anchored on the 20 to 25 BTU per square foot that ENERGY STAR’s chart works out to for an average room, then moved by IECC climate zone. The winter design temperatures are rounded zone values, not the ASHRAE 99% design condition for a specific city. A house at altitude, on a coast or in a mountain valley can sit a zone away from its nearest city.

Heating load and equipment selection

heating BTU/h = area × zone heating factor × (ceiling ÷ 8) × insulation factor × window factor

Furnace output is the smallest standard output at or above the load, from 40,000 to 140,000 BTU/h. Input is output ÷ AFUE. Blower airflow is output ÷ (1.08 × 40°F), the standard sensible heat equation for air. The furnace efficiency bands (56–70% old, 80–83% mid, 90–98.5% condensing) are DOE’s.

Heat pump sizing matches the nominal tonnage to the cooling load, then checks the heating capacity at the zone’s winter design temperature. Capacity retention is interpolated between 100% at 47°F and the ENERGY STAR floor at 5°F: 70% for a Cold Climate model, 45% for a standard model. The gap becomes backup heat in kW. Many real cold-climate models beat the floor; their published capacity table is the authority.

Mini-split sizing calculates a load per room, rounds up to the next standard head (9,000 to 36,000 BTU/h), sums the heads, then picks an outdoor unit at 85% diversity and checks that the connection ratio stays at or below 130%. The 85% and the 130% are house rules around the manufacturer connection chart. Heads above 36,000 BTU/h are rare in residential ductless equipment, which is why the tool stops there.

Duct sizing

pressure loss per 100 ft = 0.109136 × CFM1.9 ÷ diameter5.02

That is the standard ASHRAE duct friction equation for smooth galvanised duct. The calculator solves it for diameter at the chosen friction rate, then rounds up to the next standard size. The rectangular equivalent uses the equal-friction equivalent-diameter relation. The default friction rate of 0.1 in. w.c. per 100 ft and the 400 CFM per ton airflow are the conventional residential design values; California’s energy code describes 400 CFM per ton as the desired airflow and sets 350 CFM per ton as a floor for new systems.

The equation assumes clean metal. Flex duct, compressed insulation, sharp elbows and dirty filters all add resistance that the arithmetic does not see, which is why the page tells you to size one step up for flex and to design the whole system with Manual D.

Insulation

Targets come from the DOE and ENERGY STAR retrofit tables: attic R30 in zone 1, R49 in zones 2 and 3, R60 in zones 4 and colder; floor R13 to R38 by zone. The R-per-inch values used to turn R into inches — cellulose 3.5, loose fiberglass 2.5, fiberglass batts 3.4, mineral wool 3.1 — are typical installed values chosen from the ranges manufacturers publish. The bag or datasheet for the product you buy is the authority.

What we deliberately do not do

Sources

All 12 sources below were read on or before November 20, 2026. The facts listed under each one are the facts used in a calculator or on a page; anything not on this list is arithmetic or a house rule, and house rules are marked as such where they appear.

ACCA Technical Manuals — Manual J, S, D and H

Air Conditioning Contractors of America (ACCA) · read November 20, 2026 · standard

https://www.acca.org/standards/technical-manuals

  • Manual J is the ANSI-approved residential load calculation: it gives heating and cooling loads for a specific house, room by room.
  • Manual S is residential equipment selection: it matches equipment to the Manual J loads using the manufacturer's performance data.
  • Manual D is residential duct design and Manual H covers heat pump systems.
  • ACCA states that a proper load calculation is required by national building codes and by most states and municipalities.

Room Air Conditioners — sizing chart and adjustments

U.S. EPA ENERGY STAR · read November 20, 2026 · government

https://www.energystar.gov/products/room_air_conditioners

  • The published chart pairs room area with cooling capacity from 5,000 BTU/h for 100 to 150 sq ft up to 34,000 BTU/h for 2,000 to 2,500 sq ft.
  • The capacities assume an 8-foot ceiling; ENERGY STAR says to choose a higher capacity for higher ceilings.
  • A heavily shaded room can reduce capacity by 10 percent; a very sunny room should increase it by 10 percent.
  • Add 600 BTU/h for each person beyond the first two who regularly occupy the room.
  • Add 4,000 BTU/h if the unit is used in a kitchen.
  • An oversized unit cools the air before it removes humidity, which leaves the room feeling damp and clammy.

Insulation — recommended R-values by climate zone

U.S. Department of Energy, Energy Saver · read November 20, 2026 · government

https://www.energy.gov/energysaver/weatherize/insulation

  • The page maps U.S. climate zones 1 to 8 and gives recommended R-values for attics, floors and wood-frame walls.
  • Zone 1 includes Hawaii, Guam, Puerto Rico and the Virgin Islands.
  • For an uninsulated attic the recommendation runs from R30 in zone 1 to R60 in zones 4 and colder.
  • For a floor over an unheated space the recommendation runs from R13 in zones 1 and 2 to R38 in zones 7 and 8.
  • Where exterior siding is removed, DOE recommends blowing insulation into an empty wall cavity and adding continuous insulation outside the sheathing.
  • The recommendations reference the 2021 International Energy Conservation Code for climate zones.

Recommended Home Insulation R-Values

U.S. EPA ENERGY STAR · read November 20, 2026 · government

https://www.energystar.gov/saveathome/seal_insulate/identify-problems-you-want-fix/diy-checks-inspections/insulation-r-values

  • Attic targets for a retrofit: R30 in zone 1, R49 in zones 2 and 3, R60 in zones 4 and colder.
  • If the attic already has 3 to 4 inches of insulation, add R25, R38 or R49 depending on the zone.
  • Floor targets: R13 in zones 1 and 2, R19 in zones 3 and 4, R30 in zones 4C, 5 and 6, R38 in zones 7 and 8.
  • Wall guidance adds continuous insulation outside the sheathing: R5 in zone 3 and R5 to R10 in zones 4 to 8.

Furnaces and Boilers

U.S. Department of Energy, Energy Saver · read November 20, 2026 · government

https://www.energy.gov/energysaver/home-heating-systems/furnaces-and-boilers

  • AFUE is the ratio of a furnace's annual heat output to its total annual fossil fuel energy consumption.
  • An AFUE of 90% means 90% of the fuel's energy becomes heat for the home.
  • Older low-efficiency furnaces run 56% to 70% AFUE; mid-efficiency units 80% to 83%; high-efficiency condensing units 90% to 98.5%.
  • AFUE does not include duct losses, which can be as much as 35% when ducts run through an attic, garage or other unconditioned space.
  • DOE advises improving insulation and windows first, then having a contractor size the furnace, so a smaller unit can be bought.

Furnaces — key product criteria

U.S. EPA ENERGY STAR · read November 20, 2026 · government

https://www.energystar.gov/products/furnaces/key_product_criteria

  • ENERGY STAR gas furnaces are rated 95% AFUE or greater in the U.S. South and 97% AFUE or greater in the U.S. North.
  • ENERGY STAR oil furnaces are rated 87% AFUE or greater.
  • A residential furnace is defined as a unit with a heat input rate below 225,000 BTU/h.

Heat Pump Systems

U.S. Department of Energy, Energy Saver · read November 20, 2026 · government

https://www.energy.gov/energysaver/heat-pump-systems

  • A heat pump moves heat rather than generating it, so it can deliver more heat than the energy it consumes.
  • Cold-climate heat pumps are designed to perform at temperatures as low as 5°F.
  • Ductless mini-split heat pumps are a ductless air-source variant for homes without ductwork and for room-by-room zoning.
  • HSPF2 and SEER2 replaced HSPF and SEER for ratings from January 2023.

Air-Source Heat Pumps — key product criteria

U.S. EPA ENERGY STAR · read November 20, 2026 · government

https://www.energystar.gov/products/air_source_heat_pumps/key-product-criteria

  • ENERGY STAR split heat pumps are rated at least 7.8 HSPF2, 15.2 SEER2 and 11.0 EER2.
  • The Cold Climate designation requires a COP of at least 1.75 at 5°F.
  • A Cold Climate heat pump must deliver at least 70 percent of its 47°F heating capacity at 5°F.
  • A non-cold-climate heat pump is credited with at least 45 percent of its 47°F capacity at 5°F in the same criteria.

California Energy Standards Recognize the Importance of Filter Selection

U.S. Department of Energy, Building America · read November 20, 2026 · published December 17, 2014 · government

https://www.energy.gov/sites/prod/files/2014/12/f19/BA_innovations_2014__filter_sizing.pdf

  • Most residential HVAC systems operate efficiently when total static pressure stays at or below 0.4 to 0.5 in. w.c.
  • A restricted filter can push airflow below the desired 400 CFM per ton of capacity and degrade efficiency.
  • Flex duct that is compressed or sharply bent adds resistance and reduces airflow.

2025 Building Energy Efficiency Standards, Chapter 4 — residential duct and airflow requirements

California Energy Commission · read November 20, 2026 · published May 22, 2025 · government

https://www.energy.ca.gov/filebrowser/download/8636?fid=8636

  • Forced-air cooling systems must provide at least 350 CFM per ton of nominal capacity (250 CFM per ton for small-duct high-velocity systems).
  • The standards describe 400 CFM per ton and higher as the desired airflow for most systems.
  • New duct systems must be designed to ACCA Manual D or an equivalent method.

Air Distribution System Ducts, Plenums, and Fans — Manual D design practice

Energy Code Ace (California codes and standards reference) · read November 20, 2026 · industry

https://energycodeace.com/site/custom/public/reference-ace-2016/Documents/44airdistributionsystemductsplenumsandfans.htm

  • Duct systems are designed to Manual D, accounting for bends, wyes, filters, grilles and registers.
  • A typical design target is 400 CFM per ton at a fan static pressure of 0.5 to 0.6 in. w.c.
  • A typical design friction rate is 0.1 in. w.c. per 100 ft of duct.

Consumer Guide to Home Insulation

U.S. Department of Energy · read November 20, 2026 · published August 17, 2021 · government

https://www.energy.gov/sites/default/files/2021-11/ES-HomeInsulation_081721E-a.pdf

  • R-value measures resistance to heat flow; adding R-values of layers gives the assembly R-value.
  • Compressed insulation does not deliver its full rated R-value.
  • The guide gives R-value recommendations by climate zone and points to the Oak Ridge National Laboratory ZIP-code insulation program for a location-specific answer.

Corrections and review

The pages were last reviewed on November 20, 2026. If a source changes or a standard is revised, the page that uses it is updated and the reading date on this page changes. Standards that are already scheduled to change are noted in the text rather than silently applied: DOE announced a 95% AFUE federal furnace standard for late 2028, and SEER2 and HSPF2 replaced SEER and HSPF in January 2023.

If a number here disagrees with a current manufacturer document or a local code, the manufacturer document and the code win. Nothing on this site is engineering advice for a specific building.

Frequently asked

Are these calculators Manual J?

No. Manual J is a room-by-room load calculation using assembly U-values, infiltration and duct losses. These tools apply square-foot factors and published adjustments. They are screening estimates and are labelled as such on every page.

Which numbers are house rules?

The cooling and heating BTU per square foot by zone, the window and ceiling factors, the 85% mini-split diversity factor, the 130% connection-ratio cap, and the R-per-inch depths. Every one is marked house rule in the tables on this page.

Why is there no price anywhere?

No supplier publishes a national installed price for HVAC equipment, and regional prices vary by more than the equipment itself. An invented dollar figure would be worse than no figure, so this site does not publish one.

How current are the sources?

Every source on this page was read on 20 November 2026. Where a standard changes — for example the SEER2 and HSPF2 ratings that took effect in January 2023, or the 95% AFUE furnace standard due late 2028 — the page says so.

Why does a calculator disagree with my contractor?

A contractor’s Manual J uses information this site does not have: wall and window areas, insulation R-values, duct location, airtightness and orientation. A 20% to 30% difference is normal and is a reason to ask questions, not a reason to assume either number is wrong.

Back to the tools: BTU calculator · AC tonnage · furnace size · heat pump size · duct size