Furnace size calculator
The heating load of a house, the standard furnace output that covers it, and the gas input that output costs at 80, 90 or 96% AFUE — the three numbers that are constantly confused on furnace quotes.
The result below is the worked example already filled in. Change a field and press the button to see your own numbers; the result updates in place.
Your answer
60,000 BTU/h output
66,700 BTU/h input at 90% AFUE · 1,390 CFM at a 40°F rise
| Heating load | 60,000 BTU/h | 2,000 sq ft × 30 BTU/sq ft, adjusted |
| Furnace output to buy | 60,000 BTU/h | Output is the heat delivered to the house |
| Gas input required | 66,700 BTU/h | Output ÷ 90% AFUE — the number on the rating plate |
| Blower airflow | 1,390 CFM | At a 40°F temperature rise; most furnaces run 35 to 65°F |
| Duct trunk, round metal | 16 in | Supply trunk at 0.1 in. w.c. per 100 ft |
| Fuel use at full load | 0.7 therms/h | Natural gas; propane has about 91,500 BTU per gallon |
- Zone 5 — cool carries 30 BTU per sq ft in this simplified model, before the ceiling and insulation factors.
- Sizing is on output, because that is what heats the house. The input number matters for the gas line, the flue and the utility bill.
Before you buy
- Output and input are not the same number. A "100,000 BTU furnace" usually means 100,000 BTU/h input, which at 80% AFUE delivers 80,000 BTU/h.
- Do not size a replacement by the old furnace. Old units are often oversized, and a smaller, longer-running furnace is more comfortable and cheaper to run.
- AFUE ignores duct losses, which DOE puts at up to 35% when ducts run through an attic, garage or crawlspace. Fix the ducts before buying a bigger furnace.
- Above 2,000 ft elevation, gas furnaces are derated roughly 4% per 1,000 ft. The installer must set the manifold pressure and orifice for your altitude.
Sizes either side
- 40,000 BTU/h — smaller — only if the load is genuinely lower than this estimate
- 80,000 BTU/h — larger — gives headroom but costs more to run and dehumidifies worse
Input, output and AFUE: the number that trips everyone
A furnace burns gas and delivers heat, and those are two different numbers. The input is the energy in the fuel, measured in BTU per hour. The output is the heat that reaches the house. AFUE — annual fuel utilization efficiency — is the ratio between them over a typical year, and the Federal Trade Commission requires every new furnace to carry it on a label.
An AFUE of 90% means 90% of the fuel’s energy becomes heat and 10% goes up the flue. A furnace advertised as “100,000 BTU” is almost always 100,000 BTU/h input; at 80% AFUE it delivers 80,000 BTU/h. When this calculator says you need 60,000 BTU/h of output, the input at 90% AFUE is 66,700 BTU/h. Both numbers matter, for different reasons: output for comfort, input for the gas line, the flue and the bill.
| Class | AFUE | What it means in the basement |
|---|---|---|
| Older, low efficiency | 56% – 70% | Natural draft, standing pilot, metal flue |
| Mid efficiency | 80% – 83% | Induced draft fan, electronic ignition, metal flue |
| High efficiency, condensing | 90% – 98.5% | Second heat exchanger, sealed combustion, PVC vent and condensate drain |
The ranges are DOE’s. ENERGY STAR sets its own bar higher: 95% AFUE for gas furnaces in the South and 97% in the North, and 87% for oil. DOE announced in 2023 that a 95% AFUE minimum for non-weatherized gas furnaces would take effect late in 2028; the date is worth re-checking before you rely on it, but the direction is clear. Millions of 80% furnaces are still running and are not being removed.
How the heating load is estimated
The model is the same one behind the BTU calculator: heated floor area × a climate-zone heating factor × ceiling factor × insulation factor. Zone 1 starts at 10 BTU per square foot and zone 8 at 45, which reflects how much harder a Minnesota wall has to work than a Florida one. A 2,000 sq ft house in zone 5 lands at 60,000 BTU/h before rounding.
That factor is a house rule, not a published table. Manual J is the accepted method and it uses assembly U-values, infiltration and duct losses. What the rule is good for is range-checking: if a contractor proposes 120,000 BTU/h for a 1,800 sq ft house in zone 4, something is wrong, and if they propose 40,000 for a 3,000 sq ft house in zone 7, something else is wrong.
Why the furnace should usually be smaller than the old one
Furnaces installed before the 1990s were sized by rules of thumb that assumed loose houses and single-glazed windows. Many were also sized for the “worst house on the street” so the contractor would never get a callback. Add thirty years of insulation, window replacement and air sealing, and the old unit is often a size or two too big. DOE’s own advice is to improve the envelope first and then have the furnace sized, precisely because that lets you buy a smaller unit.
A smaller furnace runs longer. Longer run times mean more even temperatures, less stratification between floors, quieter operation and better use of a two-stage or modulating burner. The failure mode of an oversized furnace is the opposite: a blast of heat, a short off period, a cold far bedroom, and a heat exchanger that cycles through thermal stress for twenty years.
Temperature rise, airflow and the duct connection
Every furnace has a rated temperature rise, typically 35°F to 65°F. The blower has to move enough air to stay inside that band:
CFM = output BTU/h ÷ (1.08 × temperature rise)
For 60,000 BTU/h at a 40°F rise, that is about 1,390 CFM. If the ducts cannot pass it, the furnace overheats, the limit switch trips, and the unit short-cycles on temperature even though the house is cold. This is the most common installation fault behind “the new furnace does not keep up”. The duct calculator on this site turns the CFM into a trunk size, but a real design needs Manual D for every branch and fitting.
AFUE also stops at the furnace. DOE puts duct losses at up to 35% when ducts run through an attic, garage or crawlspace. A 96% furnace connected to leaking ducts in a 140°F attic can deliver less heat to the rooms than an 80% furnace with sealed ducts inside the envelope. Fix the ducts first.
Altitude, gas supply and the things a quote should cover
Above roughly 2,000 ft, the air is thin enough that a gas furnace must be derated, commonly about 4% per 1,000 ft, and the installer sets the manifold pressure and may change orifices. A furnace sold at sea level and installed in Denver without that adjustment runs rich and soots. The gas line also has to be sized for the input, not the output: a 100,000 BTU/h input unit needs a larger supply than the old 80,000 BTU/h one it replaced, and the existing half-inch run may not be enough.
A complete quote names the model and output, the AFUE, the venting method, the thermostat, the filter cabinet, the permit, and whether the ducts will be sealed or modified. It should also state the Static pressure and temperature rise measured at commissioning. If a quote is one line long, it is not a quote.
What this calculator cannot tell you
It does not know your duct losses, your altitude, your gas line size, your venting path or your local code. It does not model a boiler, a dual-fuel system or a heat pump. It also assumes the whole house is one zone, which is wrong for a two-storey house with a closed door at the top of the stairs. Use the number to screen quotes and to ask better questions, and let a Manual J and a Manual S equipment selection settle the purchase.
Frequently asked
What size furnace for a 2,000 sq ft house?
In zone 5 this model gives a 60,000 BTU/h heating load, so a 60,000 BTU/h output furnace. At 90% AFUE that is about 66,700 BTU/h of gas input. Colder zones and poor insulation push it to 80,000; a tight, well-insulated house can land at 40,000.
Is a 100,000 BTU furnace 100,000 BTU of heat?
Usually not. The number on the rating plate is input, the fuel burned. At 80% AFUE a 100,000 BTU/h input furnace delivers 80,000 BTU/h of heat; at 96% it delivers 96,000. Always compare the load with output.
Should I buy an 80% or a 96% furnace?
In a cold climate the condensing unit usually pays back over its life, and it vents through PVC rather than a metal flue. In a mild climate with a short heating season, the extra efficiency may never repay the price difference. The decision also depends on where the flue can run and whether a condensate drain is practical.
Can I put a 96% furnace on my old chimney?
No. A condensing furnace produces acidic condensate and flue gas cool enough that an old masonry chimney will not draft properly. It needs a sealed PVC or CPVC vent, a drain, and often a different location. That is a construction decision, not a shopping one.
Why does the blower airflow matter?
The furnace has to move the heat into the house. Airflow is set by the temperature rise: CFM = output BTU/h ÷ (1.08 × rise). Too little air overheats the heat exchanger and trips the limit switch; too much air delivers lukewarm air and can shorten the heat exchanger’s life.
My old furnace is 100,000 BTU. Can I go smaller?
Often yes, and you probably should. Old furnaces were sized by rules of thumb and are frequently oversized. A Manual J plus a review of the ducts usually allows one size down, which runs longer, quieter and more evenly.
Where these numbers come from
- Furnaces and Boilers — U.S. Department of Energy, Energy Saver, read Nov 20, 2026
- Furnaces — key product criteria — U.S. EPA ENERGY STAR, read Nov 20, 2026
- ACCA Technical Manuals — Manual J, S, D and H — Air Conditioning Contractors of America (ACCA), read Nov 20, 2026
- California Energy Standards Recognize the Importance of Filter Selection — U.S. Department of Energy, Building America, read Nov 20, 2026 (published Dec 17, 2014)
Numbers that come from our own arithmetic rather than a published table are marked house rule on the method page. No price appears anywhere on this site: no supplier publishes a national one, and an invented number would be worse than no number.
Next: heat pump sizing · BTU calculator · duct size · insulation R-value