Heat pump size calculator
The nominal tonnage to ask for, what that unit actually delivers on the coldest night, and the backup heat needed to cover the difference — the three numbers a heat pump quote usually leaves out.
The result below is the worked example already filled in. Change a field and press the button to see your own numbers; the result updates in place.
Your answer
3 tons heat pump
Delivers about 25,200 BTU/h at 5°F · 10.2 kW of backup heat
| Cooling load | 32,000 BTU/h | 2.7 tons before rounding |
| Nominal size (47°F rating) | 3 tons / 36,000 BTU/h | Matched to the cooling load |
| Winter design temperature | 5°F | Zone 5 — cool: a conservative zone value, not a city-specific ASHRAE number |
| Capacity retained at design temp | 70% | Cold-climate floor: 70% of 47°F capacity at 5°F |
| Heat delivered at design temp | 25,200 BTU/h | Nominal capacity × retained fraction |
| Heating load at design temp | 60,000 BTU/h | The house still needs this much heat on the coldest night |
| Backup heat | 10.2 kW (34,800 BTU/h) | Electric resistance strips, or a dual-fuel furnace |
| Nominal size for heating alone | 7.5 tons | At 70% retention; usually larger than the cooling size |
- The unit is matched to the 2.7 tons cooling load and checked against the 60,000 BTU/h heating load at 5°F.
- Capacity retention is interpolated between 100% at 47°F and the published floor at 5°F. Many cold-climate models do better than the floor; the manufacturer table is the authority.
Before you buy
- A heat pump is sized for cooling in most U.S. homes, with electric backup or a dual-fuel furnace covering the coldest hours. That is normal, not a failure.
- Ask for the manufacturer capacity table at your winter design temperature, not just the nominal tonnage. Capacity falls as the outdoor air gets colder.
- A cold-climate model is worth the premium where design temperatures go below 20°F; below 0°F, plan on backup heat or dual fuel.
- Sizing for heating alone would take 7.5 tons. That is above the largest common residential size, so the realistic options are dual fuel, two systems, or envelope work first.
Sizes either side
- 2.5 ton — smaller — only if the load is genuinely lower than this estimate
- 3.5 ton — larger — gives headroom but costs more to run and dehumidifies worse
A heat pump is sized twice
A furnace has one job and one rating. A heat pump has two: it cools in summer and heats in winter, and its capacity in each mode is different, and changes with the outdoor temperature. That is why a heat pump quote can be correct on tonnage and still leave a cold house in January. The nominal tonnage is measured at 47°F outdoor air for heating and 95°F for cooling. A January night is not 47°F.
The practical method is to size the unit to the cooling load, because that is the load the compressor must meet without help for hundreds of hours a year, then check the heating capacity at the local winter design temperature. Whatever gap remains is covered by electric resistance strips or by a furnace in a dual-fuel system. This calculator does exactly that and shows you the gap instead of hiding it.
Capacity at temperature, not just tonnage
Heat pump capacity falls as the outdoor air gets colder because there is less heat to extract. Manufacturers publish a capacity table: capacity and coefficient of performance at 47°F, 37°F, 27°F, 17°F, 5°F and sometimes lower. The ENERGY STAR Cold Climate designation sets a floor for that table: a COP of at least 1.75 at 5°F, and at least 70% of the 47°F heating capacity still available at 5°F. Standard models are credited with 45% in the same criteria.
Those two numbers are what the calculator interpolates between. It does not assume a particular brand. If you are comparing two models, take each one’s published capacity at your design temperature and compare that, not the nominal tonnage on the box. A “3-ton” cold-climate unit and a “3-ton” standard unit are not the same machine in February.
| Outdoor temperature | What happens to a typical air-source heat pump |
|---|---|
| 47°F | Nominal heating capacity; the number on the specification sheet |
| 32°F | Capacity is lower; the unit starts defrost cycles |
| 17°F | Cold-climate models still deliver most of their capacity; standard models are fading |
| 5°F | ENERGY STAR floor: 70% of nominal for cold-climate, 45% for standard |
| Below 0°F | Only some cold-climate models run; backup heat carries the load |
What the backup heat is for
Resistance heat is 100% efficient, which sounds good until you compare it with a heat pump running at a COP of 2 or 3: the same kilowatt-hour delivers two to three times the heat. Backup strips are for the handful of hours when the heat pump cannot keep up, and for defrost cycles. They are not meant to be the main heating system.
A well-designed system runs the strips rarely. If the calculated gap is large, the better answers are usually a cold-climate model with a stronger low-temperature table, a larger outdoor unit within the duct and electrical limits, envelope work, or a dual-fuel arrangement where the existing furnace takes over below a set outdoor temperature. The calculator reports the gap in kW so you can see what the strips would draw: 10 kW is roughly the same as four electric ovens running at once.
Cold-climate details that decide satisfaction
Defrost matters. In humid cold weather the outdoor coil frosts, and the unit reverses to melt it. A demand-defrost control reduces the number of cycles, and a unit that sits in a snowdrift or against a wall with poor drainage will spend more time defrosting than heating. Mount the outdoor unit on a stand above expected snow, keep it out of roof drip lines, and leave the clearances in the manual.
Line length and elevation also cost capacity. A long refrigerant run between the outdoor unit and an indoor coil loses capacity and needs additional charge; the installation manual gives the limits. Ducted heat pumps inherit the duct losses of the house, which DOE puts at up to 35% when the ducts run through an unconditioned attic. A ductless mini-split avoids that loss but only conditions the rooms it serves.
Efficiency ratings, briefly
SEER2 rates seasonal cooling efficiency, HSPF2 rates seasonal heating efficiency, and EER2 rates cooling at a hot design condition. Since January 2023 the ratings use tests that account for real duct resistance, so a 15 SEER unit from before the change is roughly a 14.3 SEER2 unit. ENERGY STAR split heat pumps are at least 7.8 HSPF2, 15.2 SEER2 and 11.0 EER2; cold-climate versions are at least 8.1 HSPF2 ducted or 8.5 ductless.
In a cooling-dominated climate, SEER2 and EER2 matter most. In a heating-dominated climate, HSPF2 and the low-temperature capacity table matter more. Do not buy on the headline SEER2 number alone in Maine.
What this calculator cannot tell you
It does not know your actual design temperature, your duct losses, your electrical service capacity, your defrost load or the model you are considering. The winter design temperature is a zone-level approximation, not the ASHRAE 99% value for your city; a house at 6,000 ft in zone 5 is not the same as one at sea level. It also cannot tell you whether your panel can take 10 kW of backup strips, which is a question for an electrician.
Use it to see the shape of the problem: cooling size, heating gap, backup. Then ask for the Manual J, the manufacturer capacity table at your design temperature, and the commissioning report.
Frequently asked
What size heat pump for a 2,000 sq ft house?
In zone 5 this model gives a 32,000 BTU/h cooling load, so a 3-ton heat pump. At 5°F a cold-climate unit keeps at least 70% of its 47°F capacity, about 25,200 BTU/h, against a 60,000 BTU/h heating load. The gap is normal and is covered by electric backup or a dual-fuel furnace.
Do heat pumps work below freezing?
Yes. Cold-climate models are designed to run at 5°F and some at lower temperatures, and DOE notes cold-climate heat pumps as a legitimate option for colder regions. Capacity and efficiency both fall as it gets colder, which is why the sizing question is “what does it deliver at my design temperature”, not “what tonnage is it”.
What is a balance point?
The outdoor temperature at which the heat pump’s capacity exactly equals the house’s heat loss. Above it, the heat pump keeps up alone. Below it, backup heat makes up the difference. A good design puts the balance point near the winter design temperature, not at 45°F.
Is electric backup heat a failure?
No. In most U.S. homes the heat pump is sized for cooling and the coldest hours are covered by resistance strips or a furnace. What matters is how many hours a year the strips run: a system that leans on 15 kW all winter is badly designed or badly insulated.
What is the difference between HSPF2 and SEER2?
SEER2 rates cooling efficiency over a season and HSPF2 rates heating efficiency. Both replaced the older SEER and HSPF ratings in January 2023 with tests that reflect real duct resistance. In a cold climate, HSPF2 and the low-temperature capacity table matter more than SEER2.
Should I keep my furnace and add a heat pump?
That is a dual-fuel system, and it is often the cheapest route in a cold climate: the heat pump handles most of the year and the furnace takes the coldest nights. It needs a compatible thermostat and a control strategy, so ask for the switchover temperature in writing.
Where these numbers come from
- Heat Pump Systems — U.S. Department of Energy, Energy Saver, read Nov 20, 2026
- Air-Source Heat Pumps — key product criteria — U.S. EPA ENERGY STAR, read Nov 20, 2026
- ACCA Technical Manuals — Manual J, S, D and H — Air Conditioning Contractors of America (ACCA), read Nov 20, 2026
- California Energy Standards Recognize the Importance of Filter Selection — U.S. Department of Energy, Building America, read Nov 20, 2026 (published Dec 17, 2014)
Numbers that come from our own arithmetic rather than a published table are marked house rule on the method page. No price appears anywhere on this site: no supplier publishes a national one, and an invented number would be worse than no number.
Next: AC tonnage · mini-split sizing · furnace size · method and sources