Turn airflow in CFM into the round or rectangular duct that carries it at a sane velocity and friction rate, with the standard size to install rather than the exact one to argue about.

The result below is the worked example already filled in. Change a field and press the button to see your own numbers; the result updates in place.

Your answer

16 in round duct

1,200 CFM at 0.1 in. w.c. per 100 ft · 859 ft/min · 20 × 10 in rectangular

Round duct, calculated 14.9 in Solved from the ASHRAE friction equation at the design friction rate
Round duct to install 16 in Next standard size up; never round down
Velocity, round 859 ft/min Residential trunks usually run 700 to 1,100 ft/min
Actual friction, round 0.070 in. w.c./100 ft At or below the design rate, which is the point of rounding up
Rectangular equivalent (2:1) 20 × 10 in Same friction, same airflow; wider and shallower costs more metal
Velocity, rectangular 864 ft/min Keep return ducts slower than supplies
CFM per ton equivalent 3 tons At 400 CFM per ton; a 3-ton system moves about 1,200 CFM
  • The diameter comes from the standard duct friction equation, not a manufacturer chart, so you can reproduce it: 0.109136 × CFM^1.9 ÷ diameter^5.02.
  • Rounding up to a standard size lowers the velocity and the noise, and leaves room for a slightly dirty filter.

Before you buy

  • This sizes one run. A whole system needs Manual D: every fitting, wye, boot, grille and the filter all consume pressure.
  • Flex duct is not equivalent to metal. A compressed or sharply bent flex run can lose half its capacity; pull it tight and keep bends gentle.
  • Return air matters as much as supply. Undersized returns starve the blower and raise static pressure, which is why the far rooms never feel right.
  • Keep the total external static pressure at or below the air handler rating, usually 0.5 in. w.c. A thick filter can use a large share of that.

Airflow comes first

A duct is a pipe for air, and its size follows from how much air has to move. Residential cooling is designed around 400 CFM per ton of capacity, so a 3-ton system moves about 1,200 CFM through the supply trunk and the same 1,200 CFM back through the returns. The number is not arbitrary: it is the airflow at which a typical evaporator coil transfers heat well without running so cold that it ices.

The acceptable range is roughly 350 to 450 CFM per ton. Humid climates often design at 350 so the coil runs colder and condenses more water; dry climates sometimes run 450 because latent load is not the problem. Below about 300 CFM per ton the coil can freeze and the refrigerant charge cannot be verified. California’s energy code requires at least 350 CFM per ton in its airflow verification rules for forced-air cooling systems, and 250 for small-duct high-velocity systems.

Friction rate: the number that sets the size

Air loses pressure as it moves. Duct designers describe that loss as a friction rate in inches of water column per 100 feet of duct. A lower friction rate means a larger, quieter, more expensive duct; a higher rate means a smaller, noisier one. Residential designs usually start at 0.1 in. w.c. per 100 ft, and the calculator defaults to it.

The proper value comes from Manual D: take the static pressure the blower can spare, divide it by the longest equivalent length of the worst run, and you get the friction rate for that house. A house with a short, straight run can use a higher rate; a rambling ranch with forty fittings cannot. Using 0.1 everywhere is a convention, not a design.

The equation behind the answer

The round diameter is solved from the standard duct friction equation:

pressure loss per 100 ft = 0.109136 × CFM1.9 ÷ diameter5.02

Rearranged for diameter at a chosen loss, it gives the number in the first row of the result. At 1,200 CFM and 0.1 in. w.c. per 100 ft, that is 14.9 in, which is why the recommended size is 16 in: standard round duct comes in even nominal sizes, and rounding up lowers the velocity and the noise. Rounding down would raise the friction above the design rate and put the blower further up its curve.

The rectangular equivalent uses the same idea with the equivalent-diameter formula for a rectangular section at equal friction. A 2:1 rectangle that behaves like a 14.9 in round is about 20 × 10 in. It fits between joists, but it has more surface area, more seams and more places to leak.

Velocity, noise and the rooms at the end

Velocity is airflow divided by area. Residential trunks usually run 700 to 1,100 ft/min; branch runs and returns are slower. Above about 1,200 ft/min in a trunk you start to hear the air, and at a register the noise is usually the fitting, not the duct. The result table shows velocity so you can see whether the size you are about to install is quiet or merely adequate.

The rooms at the end of the longest run get the least air. That is not a duct-sizing problem in isolation: it is a balance problem, and it is why a system needs dampers, a balancing report and, ideally, a Manual D design that treats each branch. A bigger trunk does not fix a crushed branch in a wall.

Static pressure is the real budget

Every component spends pressure: the filter, the coil, the supply plenum, each fitting, the grilles, the return. DOE’s Building America programme puts the practical total at 0.4 to 0.5 in. w.c. for most residential systems, and notes that a thick filter alone can use half of that budget. When the budget is spent before the air reaches the last room, the blower delivers less air and the system underperforms at exactly the moment it is needed.

A 1-inch fiberglass filter is cheap in both senses: it has a low pressure drop because it catches almost nothing. A high-MERV filter in a filter grille that is too small is the other extreme. The fix is filter area, not a bigger blower.

Round, rectangular, flex and where they belong

Round galvanised duct is the default for trunks and open basements: efficient, rigid, easy to seal with mastic. Rectangular duct fits in joist bays and soffits. Flex duct is fast to install and right for the last few feet to a register, provided it is pulled tight and supported. A sagging flex run is a trap for air and dust.

Whatever the shape, seal the seams with mastic or approved tape, not cloth duct tape. Duct leakage into an attic is a direct energy loss and, in a humid climate, a way to pull moist air into the house.

What this calculator cannot do

It sizes one run at one friction rate. It does not add up fittings, choose a blower, balance branches, or check the manufacturer’s maximum static pressure. It does not know whether the duct is metal, flex or ductboard, and the friction equation assumes smooth galvanised metal. For a whole system, use Manual D and a contractor who will measure static pressure after the install.

Frequently asked

What size duct for 1,200 CFM?

At 0.1 in. w.c. per 100 ft, the friction equation gives about 14.9 in, so a 16 in round duct or a 20 × 10 in rectangular trunk. A 14 in duct would be too small and noisy at that airflow, even though it is the next size down.

How many CFM is a 3-ton system?

About 1,200 CFM at 400 CFM per ton. A 2-ton system needs 800 CFM and a 4-ton system 1,600. Humid climates sometimes design at 350 CFM per ton to improve dehumidification; dry climates sometimes go to 450.

What friction rate should I use?

0.1 in. w.c. per 100 ft is the usual residential design figure and the one this calculator starts with. The right number for a specific house comes from Manual D: available static pressure divided by the longest equivalent duct run.

Is round or rectangular duct better?

Round metal is more efficient per pound of metal and easier to seal. Rectangular fits between joists and in soffits where round will not go. The calculator gives an equivalent rectangle at the same friction so you can compare, but a rectangular duct of the same friction has more surface area and more leakage potential.

Why are return ducts so often too small?

Because they are hidden and nobody complains about them until the system is loud or the far rooms are warm. A return that is smaller than the supply starves the blower, raises static pressure and drops total airflow. Size returns for the same CFM, at a lower velocity than supplies.

Can I use flexible duct?

Yes, but flex is not equivalent to metal at the same nominal diameter. Its corrugated liner adds friction, and a compressed or sharply bent run can lose a large share of its capacity. If you use flex, pull it tight, keep bends gentle and upsize one step.

Where these numbers come from

Numbers that come from our own arithmetic rather than a published table are marked house rule on the method page. No price appears anywhere on this site: no supplier publishes a national one, and an invented number would be worse than no number.