Window AC BTU calculator
The capacity a single room needs, starting from the ENERGY STAR room chart and applying the adjustments it publishes for shade, sun, people and kitchens — then rounding to a size that exists in a store.
The result below is the worked example already filled in. Change a field and press the button to see your own numbers; the result updates in place.
Your answer
14,000 BTU/h
450 sq ft in the 400–450 sq ft band · 12,200 BTU/h after adjustments
| Chart base for the room | 10,000 BTU/h | ENERGY STAR chart, 400 to 450 sq ft, 8 ft ceiling |
| Sun exposure | +10% | Very sunny rooms need 10% more |
| People | +1,200 BTU/h | 600 BTU/h for each person beyond two |
| Kitchen | +0 BTU/h | No kitchen adjustment |
| Ceiling | ×1.00 | At or below 8 ft, no adjustment |
| Calculated load | 12,200 BTU/h | Before rounding to a retail size |
| Size to buy | 14,000 BTU/h | Nearest standard size at or above the load |
- The starting point is ENERGY STAR's published band for 400 to 450 sq ft, which assumes an 8 ft ceiling and average exposure.
- Every adjustment above is one ENERGY STAR publishes, except the ceiling multiplier, which is our arithmetic on their note that taller rooms need more capacity.
Before you buy
- Bigger is not better in a bedroom. An oversized window unit reaches the thermostat before it dries the air, so the room feels cold and damp at the same time.
- Units above 12,000 BTU/h usually need a 230 V circuit. Check the plug type and the circuit before you buy; a 115 V outlet will not run a 15,000 BTU unit.
- Measure the window opening and the sash. A unit that does not fit, or that lets the sash rest on it, leaks air and vibrates.
- Look at CEER, not just BTU. A higher CEER costs less to run, and the difference over ten summers is larger than most people expect.
Sizes either side
- 12,000 BTU/h — smaller — only if the load is genuinely lower than this estimate
- 18,000 BTU/h — larger — gives headroom but costs more to run and dehumidifies worse
The chart this calculator starts from
ENERGY STAR publishes a room air conditioner sizing chart that pairs floor area with cooling capacity, assuming an 8 ft ceiling and average exposure. It is the closest thing to an official U.S. answer for a single room, and it is the base for everything below:
| Room area (sq ft) | Capacity (BTU/h) |
|---|---|
| 100 – 150 | 5,000 |
| 150 – 250 | 6,000 |
| 250 – 300 | 7,000 |
| 300 – 350 | 8,000 |
| 350 – 400 | 9,000 |
| 400 – 450 | 10,000 |
| 450 – 550 | 12,000 |
| 550 – 700 | 14,000 |
| 700 – 1000 | 18,000 |
| 1000 – 1200 | 21,000 |
| 1200 – 1400 | 23,000 |
| 1400 – 1500 | 24,000 |
| 1500 – 2000 | 30,000 |
| 2000 – 2500 | 34,000 |
The bands overlap at the boundaries: 450 sq ft is the top of the 10,000 BTU/h band and the bottom of the 12,000 BTU/h band. The calculator takes the lower band when the area falls on the boundary, then lets the adjustments move it. In practice, a 450 sq ft room in full sun rarely stays at 10,000.
The four adjustments that matter
Sun and shade
ENERGY STAR advises reducing capacity by 10% for a heavily shaded room and increasing it by 10% for a very sunny one. A west-facing room with unshaded glass is the classic case that needs the increase; a basement room or one under a deep porch is the case for the reduction. Exterior shading — a tree, an awning, a screen — is cheaper than the extra BTU and works every summer.
People
Add 600 BTU/h for each person beyond the first two who regularly occupy the room. A couple in a bedroom adds nothing; four people in a home office adds 1,200 BTU/h. Use the number who are usually there, not the number who might visit at a party.
Kitchen
Add 4,000 BTU/h if the unit serves a kitchen. A stove, an oven and a refrigerator produce heat, and a kitchen that is open to the living room is one space for this purpose. This is ENERGY STAR’s own adjustment, and it is large because cooking is concentrated heat.
Ceiling height
The chart assumes 8 ft. ENERGY STAR says to choose a higher capacity for taller ceilings, and this calculator turns that note into a multiplier of ceiling ÷ 8, capped at 1.5. It is our arithmetic rather than their table, so treat a cathedral ceiling as a reason to go up a size and to ask whether a window unit is the right tool at all.
Why oversizing is the most common mistake
A window unit has one compressor speed in most models. If it is too large, it pulls the room temperature down to the setpoint in a few minutes and shuts off. The coil never stays cold long enough to condense a meaningful amount of water, so the relative humidity stays high and the room feels clammy even though the thermometer says 72°F. Then the unit restarts, the cycle repeats, and the compressor wears.
The better answer for a room that needs steady, quiet cooling is a variable-speed unit, which can throttle down and run longer. ENERGY STAR highlights variable-speed compressors for exactly this reason. If the choice is between a cheap oversized single-speed unit and a slightly smaller variable-speed one, the smaller one is usually the better purchase.
Voltage, plug and window fit
Units up to about 12,000 BTU/h usually run on 115 V and plug into a standard outlet, but they draw close to 12 amps and should not share a circuit with a hair dryer or a space heater. Above 12,000 BTU/h, most units are 230 V and need a dedicated circuit, which is an electrician’s job. The plug shape differs by capacity: 5-15P, 6-15P and others. Check the receptacle before you order.
The window has to hold the unit. Measure the opening width and the sash height, and compare with the installation chart for the model. A unit that is too wide will not fit; one that is too narrow leaves gaps that leak air and vibrate. Most installations need a bracket or support for larger units, and many buildings restrict window units entirely.
Efficiency, noise and installation
CEER is the efficiency rating for room air conditioners: higher is better, and the difference in running cost over a decade is real. Noise is rated in decibels and is worth checking for a bedroom; compressor noise and fan noise are different, and a unit that is quiet on low may be loud on high. Look for a unit with a cleanable filter and a condensate drain path that does not drip onto the sidewalk.
Installation quality decides more than the last 500 BTU. Seal the sash with the foam and bracket supplied, tilt the unit slightly outward so condensate drains, and make sure the frame is supported so the window does not carry the weight. An unsealed unit leaks as much air as a hole in the wall.
When a window unit is the wrong tool
If the room is larger than about 2,500 sq ft, the chart stops and a single window unit stops making sense. If more than one room needs cooling, two units cost more in total and look worse than a ductless mini-split. If the house already has ducts, a central system or a ducted heat pump will be more comfortable and quieter, though it is a much larger project.
For a whole-house estimate rather than one room, use the BTU calculator or the tonnage calculator. They use the same climate logic without the room-chart bands.
What this calculator cannot tell you
It does not know the window’s U-value, the wall insulation, the shade from a neighbouring building, or how many computers run in the room. It assumes the room is closed and that the unit serves only that room. It cannot tell you whether the electrical circuit is adequate or whether the landlord allows a window unit. Those are site questions, and the answers change the purchase more than another 1,000 BTU.
Frequently asked
What size window AC for a 450 sq ft room?
The ENERGY STAR chart gives 10,000 BTU/h for 400 to 450 sq ft. A very sunny room with four people adds about 2,200 BTU/h, which pushes the answer to 14,000 BTU/h. The calculator shows both the chart base and the adjusted number.
Is a bigger window unit better?
No. An oversized unit cools the air before it removes moisture, so the room feels cold and damp, and the compressor short-cycles. ENERGY STAR makes this point directly. Choose the smallest size that covers the adjusted load.
Do I need 230 volts?
Most units up to 12,000 BTU/h run on a standard 115 V circuit. Larger units usually need 230 V, which means a dedicated circuit and often an electrician. Check the plug and the label before buying, not after.
How much does sun exposure change the size?
ENERGY STAR says to reduce capacity by 10% for a heavily shaded room and increase it by 10% for a very sunny one. That is about 1,000 BTU/h on a 10,000 BTU/h starting point — enough to change which unit you buy.
Can a window unit cool two rooms?
Only if the air can circulate. A unit in a bedroom doorway with the door open is a poor whole-house solution: the far room stays warm and the near room is over-cooled. Two small units, or a mini-split, work better.
Why does the room feel damp even when it is cool?
Because the unit is oversized or the fan is on high. A coil that is not cold enough, or a run that is too short, removes little water. Try the low fan speed on a humid day, and check that the unit is not cycling on and off every few minutes.
Where these numbers come from
- Room Air Conditioners — sizing chart and adjustments — U.S. EPA ENERGY STAR, read Nov 20, 2026
- California Energy Standards Recognize the Importance of Filter Selection — U.S. Department of Energy, Building America, read Nov 20, 2026 (published Dec 17, 2014)
- ACCA Technical Manuals — Manual J, S, D and H — Air Conditioning Contractors of America (ACCA), read Nov 20, 2026
Numbers that come from our own arithmetic rather than a published table are marked house rule on the method page. No price appears anywhere on this site: no supplier publishes a national one, and an invented number would be worse than no number.
Next: BTU calculator · mini-split size · AC tonnage · BTU per square foot